• User interface is present on the top of the SG-BWS-T4 for
signalling and configuration.
• Two units made of 8 dip-switches are present on the top of
the SG-BWS-T4-MT model. These switches activate/deactivate
and configure additional functions integrated in the device.
• Signalling interface and dip-switches are protected from non-
authorized access by transparent lids that can be opened using
a specific tool.
The EDM and MAN/AUTO Restart functions integrated in SG-BWS-T4 model can be selected through specific control unit lines
(refer “CONNECTION” section of the present document).
SETTINGS
DIP
PURPOSE
OFF (Default)
ON
1
ENABLE EDM
ENABLED
DISABLED
2
RESET MODE
AUTOMATIC
MANUAL
3
MUTING TIME-OUT
10 MINUTES
INFINITY
4
MUTING DIRECTION
T
L
2
OVERRIDE
EDGED
TRIGGERED
6
MUTING SELECTION
See specific table
7
MUTING SELECTION
8
MUTING SELECTION
INDICATORS
An user interface is present for viewing warnings and setup is present on the top of both SG-BWS-T4 and SG-BWS-T4-MT control units
Besides the 7-segment display (for diagnostics purposes), the warning components include 3 LEDs:
LED
INDICATION
POWER
Device is powered correctly
NORMAL
No danger: safety outputs closed
SAFE
Danger or fault: safety outputs open
The 7-segment display shows detailed information on control unit
current status